Sime AL 40
AL 40 on a Sime boiler means the control board has detected that the frequency of the incoming mains electricity is wrong. UK mains runs at 50 Hz, and the board checks it because its timing, pump and fan control all assume a stable supply; if the measured frequency drifts outside tolerance the boiler stops and raises AL 40. Sime's documented advice is to contact the electricity network provider, because the fault is almost never inside the boiler: it points at the property's supply — a generator or inverter supply running off-frequency, a failing UPS or backup supply, or a genuine network disturbance. The companion code AL 37 covers low supply voltage; AL 40 is specifically frequency.