Potterton E117 Fault Code: Causes, Fixes & Repair Costs

What does the Potterton E117 fault code mean?

The E117 code appears on Potterton boilers when the system water pressure has climbed above approximately 2.9 bar — well beyond the safe operating range. As a protective measure, the boiler shuts itself down and refuses to fire until the pressure is brought back within limits and the fault is cleared. Under normal conditions a cold heating system should sit between 1.0 and 1.5 bar, rising slightly to around 1.5–2.0 bar when fully warmed up. When pressure consistently exceeds that upper threshold and reaches the 2.9 bar trigger point, the boiler interprets this as a risk to internal components such as seals, pipework, and the heat exchanger, and locks out accordingly.

Lockout — engineer likely Some DIY checks possible May need a Gas Safe engineer 5 models affected

General guidance only — not a substitute for professional advice, and not certified by a Gas Safe engineer. Always have your specific appliance assessed by a qualified professional. Any gas work must be carried out by a Gas Safe registered engineer. If you smell gas or suspect carbon monoxide, leave the property and call the National Gas Emergency line on 0800 111 999.

Common causes

How to fix it

  1. Check the pressure gauge reading DIY safe

    Locate the pressure gauge on the boiler's front panel or pipework. If it reads above 2.5 bar with the heating cold, the system genuinely is overpressurised. If the gauge reads normal (1.0–1.5 bar cold) the fault may be sensor-related — note this down for the engineer.

  2. Switch the boiler off and let the system cool DIY safe

    Turn the boiler off at the controls and allow it to cool for at least 30–60 minutes before doing anything else. Never attempt to bleed radiators or adjust anything on a hot pressurised system.

  3. Bleed one or two radiators to reduce pressure DIY safe

    Using a radiator bleed key, carefully open the bleed valve on an upstairs radiator by a quarter turn. Hold a cloth or small container underneath to catch water. Air will escape first, then water will begin to drip. Watch the pressure gauge as you bleed — close the valve once the gauge drops to around 1.2–1.3 bar. Repeat on a second radiator if the pressure is still above 1.5 bar. Do not bleed below 1.0 bar.

  4. Check that the filling loop valve is fully closed DIY safe

    Locate the filling loop — usually a flexible braided hose with one or two handles beneath the boiler. Both handles should be turned so they are perpendicular (at 90°) to the pipe, indicating they are shut. If a handle feels loose, turns easily, or the hose feels warm, the valve may be passing water and will need a Gas Safe engineer to inspect or replace it.

  5. Reset the boiler DIY safe

    Once the pressure is back in the 1.0–1.5 bar range, press and hold the reset button on the boiler's control panel for 3–5 seconds until the fault code clears. Allow the boiler to attempt ignition. If E117 returns within a short period, do not keep resetting — repeated lockouts indicate an underlying fault that needs professional attention.

  6. Call a Gas Safe registered engineer if the fault persists or returns Gas Safe engineer

    If bleeding and resetting do not clear E117 permanently, or if the pressure rises again within a day or two, a Gas Safe engineer is needed. They will check the expansion vessel pre-charge pressure and recharge or replace it if necessary, inspect and replace a faulty filling loop valve, test and replace the pressure relief valve or pressure sensor, and carry out a full system health check to establish why pressure keeps climbing.

Parts you may need

The exact spare depends on your boiler's GC number (on the data badge). Check this against the part before buying.

Typical repair cost

Expect to pay roughly £100–£300, depending on the underlying cause.

Frequently asked questions

Can I fix Potterton E117 myself without calling an engineer?

Some initial steps are safe for a homeowner to try: checking the pressure gauge, bleeding a radiator to bring the pressure down to around 1.2 bar, making sure the filling loop is closed, and doing a single reset. If the pressure drops to a normal level and stays there, the boiler may well be fine. However, if the fault returns, or if the pressure keeps climbing on its own, the underlying cause — a failed expansion vessel, a leaking filling loop valve, or a faulty PRV — needs a Gas Safe registered engineer to diagnose and fix properly.

Why does my Potterton boiler keep going over pressure even after I bleed the radiators?

If the pressure creeps back up after you've bled it down, something is continuously adding water to the system. The most likely culprit is a filling loop valve that isn't sealing properly, allowing mains water to slowly trickle in. A failed expansion vessel diaphragm is another common reason — without a functioning vessel to absorb expansion, pressure spikes every time the boiler heats up. Both faults need a Gas Safe engineer to confirm and fix.

Is high boiler pressure dangerous?

Sustained high pressure puts extra stress on seals, pipe joints, and the heat exchanger, which can lead to leaks over time. Modern boilers like Potterton models have a pressure relief valve that should discharge water safely outside the property if pressure becomes extreme, but a PRV that has opened once may not reseal reliably. This is why the boiler locks out at E117 — it is a built-in safety measure. Don't ignore it or repeatedly reset without addressing the root cause.

How much does it cost to fix a Potterton E117 fault?

Most E117 repairs in the UK fall between £100 and £300 including labour. Recharging or replacing an expansion vessel typically costs £100–£200, a filling loop valve replacement around £100–£200, and a pressure relief valve or pressure sensor replacement in the £150–£250 range. If a more significant component such as the PCB or heat exchanger is involved (which is uncommon for a pressure fault), costs can be higher — discuss this with your engineer before authorising any major work, especially on an older boiler.

Affected models: Potterton Titanium, Potterton Promax, Potterton Performa, Potterton Gold, Potterton Profile

Last reviewed 1 July 2026 · verified by our team.

Are you a heating engineer? Join our network and get local jobs sent to you.

Find a Gas Safe engineer

✓ Your boiler details: Potterton E117 — one step done already.

We pass your details to up to 3 vetted local engineers. No payment is taken here.

Can't find your boiler or fault code?

Tell us what you need — we'll help, and we can put you in touch with a Gas Safe registered engineer.

Get in touch →