Nibe 155 Fault Code: Causes, Fixes & Repair Costs

What does the Nibe 155 fault code mean?

Fault code 155 is the Hot Gas Alarm. It activates when the discharge temperature sensor BT14 detects that the hot gas leaving the compressor has climbed above 135°C. At that point the heat pump shuts the compressor down to protect the refrigerant circuit from damage. The alarm clears itself automatically once the discharge temperature falls back below 90°C. Because the compressor is the most expensive component in the system, this self-protection trip should always be taken seriously — especially if it keeps coming back.

Stop & check now 9 models affected

General guidance only — not a substitute for professional advice, and not certified by an heat pump engineer. Always have your specific appliance assessed by a qualified professional. Any heat pump work must be carried out by an MCS-certified heat pump engineer. If you notice a refrigerant leak, a burning smell or water leaking from the unit, switch it off at the isolator and call an MCS-certified heat pump engineer. Refrigerant work must be carried out by an F-Gas registered engineer.

Common causes

How to fix it

  1. Check the area around the outdoor unit and clear any obstructions DIY safe

    Walk outside and look at the outdoor unit. Remove any leaves, garden debris, snow or ice covering the coil grille or blocking the fan outlet above. Ensure there is at least 30–40 cm of clear space on all sides. Poor airflow is a quick win that is easy to rule out before calling anyone.

  2. Allow the unit to cool and wait for the auto-reset DIY safe

    Fault code 155 resets itself once the discharge temperature drops below 90°C. Do not repeatedly press reset while the unit is still hot — this risks further stress on the compressor. Wait at least 15–20 minutes after the alarm appears before attempting any manual reset.

  3. Attempt a single manual reset via the controller DIY safe

    On your Nibe display, select the fault message, choose 'I want to see more information about this alarm' and then select 'Reset alarm and try again.' The controller will restart and the heat pump will attempt to return to normal operation. If the fault clears and does not return within the next hour, continue to monitor it. If it immediately reappears or returns within the same hour, do not reset again.

  4. Check system water pressure DIY safe

    While you are waiting, glance at the system pressure gauge on the indoor unit or buffer vessel. It should typically read between 1.0 and 1.5 bar when cold. A low-pressure reading may indicate a separate issue contributing to poor heat transfer. Top up via the filling loop if needed, following your system's instructions.

  5. Do not attempt further resets if the alarm keeps returning — call an MCS-certified heat pump engineer heat pump engineer

    If fault code 155 returns after a single reset, the underlying cause almost certainly involves the refrigerant circuit, the expansion valve or the BT14 sensor — none of which are safe or legal for a homeowner to investigate. Contact an MCS-certified heat pump engineer, and note that any work on the refrigerant circuit (leak testing, pressure checks, topping up or recovering refrigerant) must be carried out by an F-Gas registered engineer. Nibe also has a network of Approved Repair Partners trained specifically on Nibe systems who can be reached via the Nibe homeowner care line on 0330 311 2201.

Parts you may need

The exact spare depends on your boiler's GC number (on the data badge). Check this against the part before buying.

Typical repair cost

Expect to pay roughly £150–£550, depending on the underlying cause.

Frequently asked questions

Will my Nibe heat pump restart on its own after fault code 155?

Yes, the alarm is designed to clear automatically once the BT14 sensor reads below 90°C, so the system will often attempt to restart by itself. However, if the root cause has not been resolved — such as a low refrigerant charge or a stuck expansion valve — it is very likely to trip again soon after. A single manual reset is reasonable, but if the fault returns within the same hour you should stop resetting and get an engineer involved to avoid putting repeated strain on the compressor.

Could a refrigerant leak cause fault code 155, and how much does it cost to fix in the UK?

A refrigerant leak is one of the most common reasons for a persistent hot gas alarm. When the circuit is low on refrigerant the compressor works harder and discharge temperatures spike. Diagnosing and repairing a leak typically costs between £200 and £500 for most accessible joints and connections, including an F-Gas compliant leak test and recharge. In more complex cases — where the leak is on the outdoor coil or requires significant pipework repair — costs can rise to around £800–£1,200. Only an F-Gas registered engineer can legally handle refrigerant in the UK.

What is the BT14 sensor and can it cause a false alarm?

BT14 is the discharge or 'hot gas' temperature sensor fitted to the compressor outlet pipe. It measures the temperature of refrigerant leaving the compressor and feeds that reading to the Nibe control board. If the sensor develops a fault, a loose connection or a broken wire, it can report a falsely elevated temperature and trigger fault code 155 even when the actual discharge temperature is fine. A qualified engineer can check the sensor's resistance against Nibe's reference values to confirm whether it is reading correctly. Sensor replacement including labour typically costs in the region of £130–£250.

Is fault code 155 dangerous — should I be worried about my heat pump?

The alarm itself is a safety feature, so the system is doing exactly what it is designed to do by stopping the compressor before damage occurs. There is no immediate danger to your home. However, ignoring a repeated hot gas alarm can lead to premature compressor failure, which is by far the most expensive repair on a heat pump — typically £1,200 to £2,500 or more depending on the model. Treating the fault promptly, rather than repeatedly resetting it and hoping for the best, is strongly advisable.

Affected models: Nibe F2040, Nibe F2120, Nibe S2125, Nibe F730, Nibe F1145, Nibe F1245, Nibe F1345, Nibe SMO 20, Nibe SMO 40

Last reviewed 2 July 2026 · verified by our team.

Are you a heating engineer? Join our network and get local jobs sent to you.

Find a heat pump engineer

✓ Your boiler details: Nibe 155 — one step done already.

We pass your details to up to 3 vetted local engineers. No payment is taken here.

Can't find your boiler or fault code?

Tell us what you need — we'll help, and we can put you in touch with a Gas Safe registered engineer.

Get in touch →